 DRAFT NELSON
JobN075236 Date:28/04/08
NGC-30-CR NGC-30-CRM NGC-30-CRMS NGC-30-CTM NGC-30-CVM
Document Install-113
Installation Instructions Montageanleitung Instructions d'installation
www.DataSheet.in
NGC-30-CR NGC-30-CRM NGC-30-CRMS NGC-30-CTM NGC-30-CVM
Installation Instructions Description
Control and monitoring modules for use with DigiTrace NGC-30
the Digitrace(R) nGC-30 is a multi-circuit electronic control, monitoring and power distribution system for heat-tracing used in process-temperature maintenance and freeze-protection applications. the nGC-30-CRM/-CRMs and nGC-30-CtM provide ground-fault and line current sensing, alarming, switching and RtD inputs for five heat-tracing circuits when used with the nGC-UIt. the nGC-30-CRM is to control electromechanical relays (EMRs) and the nGC-30-CRMs is used to control solid state relays (ssRs). Tools Required * screw driver small blade - standard * RJ11 stripping/crimping tool * Wire cutters * RJ11 connectors
Additional Materials
* Power supply - 12 Vdc @ 400 ma-per nGC-30-CRM/-CRMs board * RJ11 4 conductor cable
Kit Contents
Item a B C D
General approvals/Certifications Non-hazardous Locations Hazardous Locations supply Voltage Internal power consumption ambient operating temperature ambient storage temperature Environment Max. altitude Humidity Electromagnetic Compatibility Emission
Class I, Div. 2, Groups A,B,C,D Ex nC IIC T5 Class I, Zone 2, AEx nC IIC T5
Qty 1 1 1 1
Description nGC-30-CRM or CRMs (card rack module with connectors) nGC-30-CtM (current transformer module) nGC-30-CR (card rack) nGC-30-CVM (voltage monitoring module) - optional
Din Rail - 35 mm Five for ground-current measurement Five for line current measurement 60a 2% of reading 10 - 200 ma 2% of range 80 - 290 Vac 50/60 Hz 1% of span Form a 3-amp @ 277 Vac max 50/60 Hz 12 Vdc @ 30 ma max per output sPDt 3-amp @ 277 Vac max 50/60 Hz 2 wire Rs-485 One shielded twisted pair 1200 M (4000 ft.) maximum Up to 52* nGC-30-CRM/-CRMs may be connected to one nGC-UIt 0.8 - 3.3mm2
Current Sensors Mounting Quantity per nGC-30-CtM Line Current Sensors Max current accuracy Ground Fault Sensor Range accuracy Voltage Sensor Range accuracy Outputs CRM output relays CRMs ssR outputs alarm Relay Communication to NGC-UIT type Cable length Quantity Connection Terminals Power supply/Pilot Relay/ RtD/Comm Port (Rs485)
* May require repeaters
12 Vdc 10% < 5 W per nGC-30-CRM/-CRMs -40C to 60C (-40F to 140F) -40C to 75C (-40F to 167F) PD2, Cat III 2000 m 0 - 90% non-condensing tested to Class a (Industrial Environments). Under CE standard En 61000-6-4:2001 tested to En 61000-6-2 100-ohm platinum RtD, 3-wire, = 0.00385 ohms/ohm/C Can be extended with a 3-conductor shielded cable of 20 ohm maximum per conductor Up to 5 3-wire pt100s wired directly to each nGC-30-CRM/-CRMs
Immunity Temperature Sensors type
Quantity
WARNING:
this component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions. * Component approvals and performance are based on the use of tyco thermal Controls-specified parts only. Do not use substitute parts. * Keep components dry before and during installation. * leave these instructions with the end user for reference and future use. For technical support, call tyco thermal Controls at + 00 32 16 213511 or your local representative.
www.DataSheet.in
Cleaning Instructions
If dust accumulates on the nGC-30-CRM/-CRMs circuit board use dried compressed air to remove the dust. turn off all power to the nGC-30 panel. Carefully disconnect all cables from a single nGC-30-CRM/-CRMs card, making sure to label cables so that they can be reconnected after board cleaning. Wear an anti-static wrist strap connected to ground in order to avoid component damage. Remove the CRM/CRMs circuit card from the card cage and place on a clean lint-free surface. Use dry compressed air from a can for cleaning circuit boards. (avoid factory compressed air since it may contain enough moisture or oil to cause permanent damage.) Use short quick blasts to remove dust buildup as necessary. after cleaning, replace the CRM/CRMs in the same card cage position and reconnect all cables. Remove only one card at a time for cleaning to avoid any problems during re-installation.
NGC-30-CR Installation Instructions Mounting of Card Rack
Use the mounting template (on page 7) to mount the rack on a panel backplane. there are four holes (0,48 cm dia.) to secure it to the mounting surface using #8 screws. Once the card rack is installed, a earth bonding wire must be connected to the card rack using the ground screw provided. Note: the card rack must be installed on a non-combustible surface.
283 mm (11.15") 183 mm (7.20")
279 mm (10.97")
Grounding screw
NGC-30-CRM/-CRMS Installation Instructions
NGC-30-CRM/CRMS
bk
MSB LSB
9
TB 1
123
TB 2
TB 3
TB 4
TB 5
TB 19 TB 12 TB 7 TB 6 TB 13 TB 14 TB 15 TB 16 TB 17
1
2
3
456 7
8
1 2 3 4 5 6 7 8
Alarm output Relay outputs (5x) LEDs (9x) Fuse 12 Vdc Inputs (2x) End of Line (EOL) jumper RS-485 Communications Line & ground-fault sensor inputs (5x) 9 RTD Inputs bk Address Switches
Relay 1 Relay 2
Relay 3 Relay 4
Power
Tx Relay 5 Rx
Alarm
LED functions
178 mm (7.00")
273 mm (10.75")
4
DIGItRaCE nGC-30 InstallatIOn InstRUCtIOns
www.DataSheet.in
Power Supply
the power supply connector (tB19) is a dual two pin connector. Either connector allows for power in (pin #1 (+), pin #2 (-) and bussing of power to other nGC-30-CRM modules). Note: Power supply must be sized correctly based on the number of nGC-30-CRM/-CRMs modules.
1
21
2
this connector switches voltage to the contactor coils or solid state relays. the pilot relay will switch the supply voltage (up to 277 Vac) to the contactor coil (using an nGC-30-CRM) or 12 Vdc to the solid state device (using an nGC-30-CRMs).
Relay Output Connections to Contactors or Solid State Devices (TB7)
10-RLY3 8-RLY2 12-RLY4
7 8 9 10 11 12
1
2
3
4
5
6
1-COM
6-RLY5 3-RLY1
Refer to system layout diagram for detail wiring.
the Rs-485 connector (tB6) is a dual three pin connector. Either connector allows for Rs-485 input signals (pin #1 (shield), pin #2 (+), pin #3 (-)) and bussing of Rs485 signal to other nGC-30-CRM modules.
RS-485 Communications
Common Alarm
the common alarm terminal block (tB12) provides a form C dry contact, rated at 277 Vac max (3a).
123 123
End of Line (EOL) Jumper
When the Digitrace nGC-30 system is powered on, the common alarm relay coil is energized and pin 2 is connected to pin 1 (common). this is the "no alarm" condition for the CRM/CRMs board. If the alarm occurs, or the CRM/CRMs board loses power, the relay coil is de-energized and pin 1 (common) is disconnected from pin 2 and connected to pin 3 to indicate an alarm condition exits.
123 COM N.C. N.O.
If this device (nGC-30-CRM/-CRMs) is the last device in the Rs-485 network, the J1 jumper needs to be moved from terminals 2 & 3 to terminals 1 & 2.
Normal position 1 2 3
End of Line position 1 2 3
Relay "no alarm" Condition
RTD Inputs - Ordinary Area
3 wire RtDs with shield may be connected to RtD Ch1 thru Ch 5 (tB1 - tB5). the two common wires (usually red, red) are connected to terminals 2 & 3, the source (usually white) to terminal 1 and the braid to terminal 4 (earth ground). Note: RtD's are not required if monitoring current/ground-faults only or if RtD's are connected via MOnI-RMM2s.
Each nGC-30-CRM/-CRMs must have a unique communication address selected. the valid address switch range when using the nGC-UIt is 1-99. sW1 is the ones digit (0-9) and sW2 is the tens digit (0 or 9). Note: When adding an nGC-30-CRM/-CRMs to the system, you must perform a network update at the nGC-UIt.
Address Switches (SW1 & SW2)
MSB
8
LSB
3
SW2
SW1
1234
RTD connected directly to CRM board RTD
1 2 3 4
Connections from nGC-30-CRM/-CRMs to nGC-30-CtM.
RTD1 Shield RTD2 Shield RTD3 Shield RTD4 Shield RTD5 Shield
Ground-Fault/Line Current Sensors
Using an RJ11 connector/cable assembly, connect one end to an RJ11 input (tB13-tB17) and the other end to the appropriate nGC-30-CtM RJ11 connector.
8
RTD
1 2 3 4
Typical connection (1 of 5)
RTD
1 2 3 4
CRM PCB
RTD
1 2 3 4
RTD
1 2 3 4
Ground-Fault/Line Current Cable Assembly
Cables are not available as loose item. they need to be created by the project team while assembling the panel.
Chassis Ground
(L)
DIGItRaCE nGC-30 InstallatIOn InstRUCtIOns
5
www.DataSheet.in
Optional Voltage Sensor
Cable Preparation
Notes: 1. Cut one end off of a groundfault /line current cable. 2. strip insulation approx. 2,5 cm from cut end. 3. strip the red and black wire insulation approx. 0,5 cm. 4. Connect red and black wire to the two position terminal plug. no need to be concerned about polarity. 5. wtrim brown and orange wires from cut end.
the optional voltage sensor can monitor 80 - 290 Vac. this voltage connects to one of the five line current/ground-fault inputs on the nGC-30-CRM. Note: By using the optional voltage sensor, you lose the ability to monitor the ground-fault and current for that circuit.
Mounting of NGC-30-CTM
Each nGC-30-CtM mounts on a DIn 35 rail. It should be located between the circuit breaker or terminal block and contactor or ssR in the panel.
NGC-30-CTM Installation Instructions
6
DIGItRaCE nGC-30 InstallatIOn InstRUCtIOns
www.DataSheet.in
System Layout NGC-30-CRM System Layout NGC-30-CRM
12Vdc 230 Vac in Power Supply
NGC-UIT Touch Screen
230 Vac contctor power L N
RTDs
Alarm relay output AC voltage up to 277 Vac
NGC-30-CRM
Distribution panel board with standard circuit breakers L N To contactor coils (see detail) NGC-30-CTM
o1 o2 o3 N
230 Vac Relay drivers 1 1 2 3 4 5 3 8 10 12 6
Pilot relays Contactor located on coils circuit board
DIGItRaCE nGC-30 InstallatIOn InstRUCtIOns
To heater's power junction box
7
www.DataSheet.in
System Layout NGC-30-CRMS
System Layout NGC-30-CRMS
12Vdc 230 Vac in Power Supply
NGC-UIT Touch Screen
RTDs
Internal 12 Vdc SSR power Alarm relay output AC voltage up to 277 Vac NGC-30-CRMS
Note: 12Vdc power provided by NGC-30-CRMS board Internal 12 Vdc
To SSR DC input (see detail) SSR NGC-30-CTM
Distribution panel board with standard circuit breakers
o1 o2 o3 N
-
+
1 3
SSR SSR
1 Output driver
SSR SSR
2 3 4 5
8 10 12 6
SSR SSR SSR SSR
SSR
SSR
SSR To heater's power junction box (typical 5)
8
DIGItRaCE nGC-30 InstallatIOn InstRUCtIOns
www.DataSheet.in
www.DataSheet.in
Top of Card Rack
DIGItRaCE nGC-30 InstallatIOn InstRUCtIOns
NGC-30-CR Wall mounted hole template
(Note: Ensure the printed template has scaled correctly.
18 cm (7.00")
25 cm (9.75")
o 0,5 cm
(0.188")
1,5 cm (0.625")
9
6,2 cm (2.4")
General Installation Instructions
1. the nGC-30 components must be installed: * In compliance with all local electrical and safety codes * In an enclosure suitable for the application environment. When used in hazardous (Class I, Div. 2 or Zone 2) locations, a minimum IP54 enclosure is required. 2. the nGC-30 components must be protected by external overcurrent and disconnect devices. this may be a circuit breaker or a combination of disconnect switch and fuses. the disconnect device: * Must disconnect all ungrounded, current-carrying conductors * should be located in close proximity to the equipment * Be within easy reach of the Operator * Be marked as the disconnecting device for the equipment 3. supply wiring insulation must be rated for the highest voltage and temperature to be encountered in the application. Conductors must be sized for the application and be protected by an external overcurrent device. 4. some wiring configurations will use more than one power source and all must be de-energized prior to performing any maintenance on a controller circuit. 5. Protection provided by this equipment may be impaired if the device is used outside of its ratings or for applications other than is intended. 6. always be sure that the intended location is classified as an area for which the product is approved. 7. CRM(s) and CtM modules must be handled with care when installed in a panel. Components should not be subject to mechanical stress. 8. Wear an anti-static wrist strap connected to ground in order to avoid component damage when installing the CRM(s) or CtM modules.
Conducted And Radiated Emissions - Statement Of Compliance
this equipment has been tested and found to comply with the limits for a Class a digital device, pursuant to Part 15 of the FCC Rules. these limits are designed to provide reasonable protection against harmful interference in a residential installation. this equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. - Consult the dealer or an experienced radio/tV technician for help. this Class a digital apparatus complies with Canadian ICEs-003.
10
DIGItRaCE nGC-30 InstallatIOn InstRUCtIOns
www.DataSheet.in
European Headquarters Tyco Thermal Controls Romeinsestraat 14 3001 Leuven Belgium Tel. (32) 16 213 511 Fax (32) 16 213 610 info@tycothermal.com Belgie / Belgique Tyco Thermal Controls Romeinsestraat 14 3001 Leuven Tel. (016) 213 502 Fax (016) 213 604
Italia Tyco Thermal Controls SPA Centro Direzionale Milanofiori Palazzo F1 20090 Assago, Milano Tel. + 39 02 57761520 Fax + 39 02 57761528
ROSSIA i drugie strany SNG 000 Tajko Termal Kontrols Rossia, 127081, Moskva pr. Deoneva 29/1 Tel. (495) 508 99 75 Faks (495) 508 99 74 Schweiz / Suisse Tyco Thermal Controls N.V. Office Baar Haldenstrasse 5 Postfach 2724 6342 Baar Tel. (041) 766 30 80 Fax (041) 766 30 81 Serbia and Montenegro Keying d.o.o. Vuka Karadia 79 23300 Kikinda Tel. (230) 401 770 Fax (230) 401 790
Lietuva/Latvija/Eesti Tyco Thermal Controls BV Atstovybe Smolensko g. 6 LT-03201 Vilnius Tel. +370 5 2136633 Fax +370 5 2330084 Magyarorszag Szarka Ignac Maroshevisz u. 8 1173 Budapest Tel. (1) 253 76 17 Fax (1) 253 76 18
Bulgaria ERZET Engineering Kompl. Bratja Miladinovi/bl57/vch.4A BG-8000 Burgas Tel./fax (56) 86 68 86 Mobile (88) 86 39 903 Fax (UK) +44 8701368787 Ceska Republika Raychem HTS s.r.o. Novodvorska 82 14200 Praha 4 Tel. 241 009 215 Fax 241 009 219
Nederland Tyco Thermal Controls b.v. Van Heuven Goedhartlaan 121 1181 KK Amstelveen Tel. 0800 0224978 Fax 0800 0224993
Danmark Tyco Thermal Controls Nordic AB Flojelbergsgatan 20B SE-431 37 Molndal Tel. 70 11 04 00 Fax 70 11 04 01 Deutschland Tyco Thermal Controls GmbH Birlenbacher Strasse 19-21 57078 Siegen-Geisweid Tel. 0800 1818205 Fax 0800 1818204
Norge Tyco Thermal Controls Norway AS Postboks 6076 - Etterstad 0601 Oslo Tel. +47 66 81 79 90 Fax +47 66 80 83 92 Osterreich Tyco Thermal Controls Division of Tyco Fire & Integrated Solutions GmbH Office Wien Brown-Boveri Strasse 6/14 2351 Wiener Neudorf Tel. (0 22 36) 86 00 77 Fax (0 22 36) 86 00 77-5
Suomi Tyco Thermal Controls Nordic AB Flojelbergsgatan 20B SE-431 37 Molndal Puh. 0800 11 67 99 Telekopio 0800 11 86 74 Sverige Tyco Thermal Controls Nordic AB Kanalvagen 3 A SE-194 61 Upplands Vasby Tel. 08-590 094 60 Fax 08-590 925 70
Espana Tyco Thermal Controls N.V. Ctra. De la Coruna, km. 23,500 Edificio ECU I 28290 Las Rozas, Madrid Tel. (902) 125 307 Fax (91) 640 29 90 France Tyco Thermal Controls SA B.P. 90738 95004 Cergy-Pontoise Cedex Tel. 0800 906045 Fax 0800 906003 Hrvatska ELGRI d.o.o. S. Mihalica 2 10000 Zagreb Tel. (1) 6050188 Fax (1) 6050187
Polska Tyco Thermal Controls Polska Sp. z o.o. ul. Cybernetyki 19 02-677 Warszawa Tel. 0 800 800 114 Fax 0 800 800 115 Republic of Kazakhstan Tyco Thermal Controls 4 Khakimov St. Atyrau, 060002 Tel. +7 7122 32 56 51 Fax +7 7122 32 56 38
United Kingdom Tyco Thermal Controls (UK) Ltd 3 Rutherford Road, Stephenson Industrial Estate Washington, Tyne & Wear NE37 3HX Tel. 0800 969013 Fax: 0800 968624 Worldwide Headquarters Tyco Thermal Controls 2415 Bay Road Redwood City, CA 94063-3032 USA Tel. (1)(650) 216-1526 Fax (1)(650) 474-7711 info@tycothermal.com
Romania
Tyco Thermal Controls Romania 53 Primaverii Bvd. 011973 Bucuresti Tel. 21 317 92 87 Fax 21 317 92 87
www.tycothermal.com
Digitrace is a trademark of tyco thermal Controls, llC or its affiliates. Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect or consequential damages arising from the sale, resale, use or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes, without notification to the Buyer, to processing or materials that do not affect compliance with any applicable specification.
www.DataSheet.in
(c) 2006 Tyco Thermal Controls INSTALL-113 Rev.2 04/08 Printed in Belgium on chlorine-free bleached paper.
Turkiye SAMM Di Ticaret A.. Yeniyol Sk. Etap Merkezi C Blok No: 10 Kat : 6 34722 Acibadem - Kadikoy STANBUL Tel : +90-216-325 61 62 (Pbx) Faks : +90-216-325 22 24


▲Up To Search▲   

 
Price & Availability of NGC-30-CXX

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X